pH measuring and controlling instrument
This measuring instrument can be used to sense the value of pH continuously in high accurace province, with the help of single, or combined electrodes.
SPECIFICATION | |
---|---|
2xS.5-F-pH | sleeved for the wall one current out |
2xS.5-T-pH | sleeved for the table one current out |
…-pHimp… | Two impulse out |
2xS.5-…-pHI | Two current out |
Measurement range pH: | 0-14pH |
– Accuracy: | ±0,01pH ±1digit |
Adjustable asymmetric: | 6-8 pH |
Input impedance: | >1012 Ω |
Temperature compensation: | automatics/manuals |
Measuring range -T: | 0-200 °C |
Temperature sensor: | Pt100 |
– Accuracy: | ±0,2 °C ±1digit |
Current output: | 0/4..20mA Rtmax=500Ω |
– 2. Current output : | option 2xS-..-pHI |
Adjustable output parameter: | pH or T |
Input is isolated from the output. Isolation is galvanic. | |
Limits outputs: | morse contact relay |
Minimum and maximum limiting value: | Between 0-14pH is adjustable |
Hysteresis: | adjustable |
– Power supply: | 230V AC 3A (Φ=1) |
Digital out: | RS232/RS485 (option) |
Power supply: | 230V AC ±10% 50-60Hz 6VA,II. ÉVO |
Ambient temperature: | -20..+50°C |
Protecting: -F- type | PC:IP65 |
.-T-.. type on-board | IP 44 |
..-T-.. típ. back-board | IP 20 |
. Size: ..-F-.. type | 165x155x96mm, PC:166x160x106 |
…-T-.. type | 144x72x146mm |
.-T-.. type exsection’s size | 138,3x67mm |
Weight: | approx.1Kg |
Electrodes: pH | Single and combined electrode |
T | Pt100 |
Armatures: | immersion and flow-through |
Tying up
IMMERSION cell
pH Redox-potential Conductivity elektrodes
with 1 or 2 electrodes
Pipe diameter:
with 1 electrode: 40 mm
with 2 electrodes: 63 mm
Adjustable immersion
Material of measuring cell:PVC
Material of bracket:PP or pipe ring
FLOW-THROUGH cell
pH Redox-potential Conductivity elektrodes
Pipe diameter:
-with 1 electrode: 40 mm
-with 2 electrodes: 63 mm
Material of measuring cell:PVC
Size of female pipe:
-in case of 1 electrode: G5/4″
-in case of 2 electrodes: G2″
FLOW-THROUGH cell built in pipe
Terminal inner size:
-in case of 1 electrode: G5/4″
-in case of 2 electrodes: G2″